ACC2
Ashburn, VA
Completed in 2005, ACC2 is situated on 22 acres of land at the Ashburn Corporate Center Phase I Condominium in Loudoun County, Virginia. The facility is located within a half mile of the corporate offices of Verizon (formerly MCI's world headquarters) and America Online's corporate headquarters. Loudoun County is the fastest growing county in the region and the eighth fastest growing county in the U.S. ACC2 comprises approximately 87,000 gross square feet and 53,397 raised square feet, with an aggregate critical load of 10.4 MW evenly divided between two computer rooms. In 2000, we acquired the undeveloped land related to ACC2 and developed ACC2 as an empty shell. The shell was leased from mid-2001 through late 2003 to a provider of colocation services. Thereafter, ACC2 was vacant. In the first quarter of 2005, we began developing the infrastructure of ACC2, and in October 2005 we completed development and brought the property into service as a wholesale data center.
Specifications
| Property | |
|---|---|
| Location | Ashburn, VA |
| Completed | 2005 |
| Acreage | 6.79 |
| Building Size (sq ft) | 84,971 |
| Nearest Airport | 7 Miles from Dulles International Airport |
| Critical Power | |
| Total MW | 10.4 |
| Building Description | |
| Parking | 208 |
| # of Stories | 1 |
| Loading Area and Docks | 2 Loading Bays |
| Elevators | 1 Freight Elevator |
| Ceiling Height | 10 ft |
| Data Center Area Description | |
| Raised Floor Area | 59,400 |
| # of Quadrants | 2 |
| Raised Floor Height | 42" |
| UPS Systems | |
| Description | 10 Rotary power systems with 1,300 kW of critical output, 500 kW of essential output |
| Redundancy | N+2 redundancy |
| Generators | |
| Description | 4 diesel-powered emergency generators with 2,000 kW capacity |
| Redundancy | N+1 |
| Utility Power | |
| Dominion Virginia Power - 34.5 kV | |
| Heat Rejection systems (AC) | |
| Description | Air cooled chilled water cooling system, capacity 4,000 Tons |
| Redundancy | N+2 |
| On site Fuel | |
| # of Gallons | 84,000 gallons |
| # of Hours | 48 Hours |
| Fire Protection | |
| Extensive pre-action zoned dry-pipe fire protection system with subfloor, room, and above ceiling smoke detectors | |
| Security | |
| Building and Perimeter | Bullet resistant protection at security check-in, front window areas and loading dock |
| Space Security | Staffed 24/7 with separate security lobby |
| Access Control | Electronic Security features with card key access |
| Alarm System | Yes |
| CCTV | Camera Surveillance |
| PDUs | |
| 300-kVA Power Distribution Units with Integral Static Transfer Switches | |
| Tenant Office Space | |
| Available | |
| Communications | |
| 2 redundant POE's for Carriers with no single point of cable plant failure | |
| Expansion Potential | |
| No | |