ACC3
Ashburn, VA
Completed in 2006, ACC3 is situated on 22 acres of land at the Ashburn Corporate Center Phase I Condominium in Loudoun County, Virginia. The facility comprises approximately 147,000 gross square feet and 79,600 raised square feet, with an aggregate critical load of 13.0 MW divided among four computer rooms, with 3.9 MW available to each of two computer rooms and 2.6 MW available to each of the remaining two computer rooms. In 2000, we acquired the undeveloped land related to ACC3 and developed ACC3 as an empty shell. The building was briefly leased to a provider of colocation services. This lease was terminated in early 2002 and ACC3 remained vacant. We began to develop the wholesale infrastructure of this facility in December 2005 and brought it into service in as a wholesale data center in June 2006. As of August 1, 2007, ACC3 was 100% leased.
Specifications
| Property | |
|---|---|
| Location | Ashburn, VA |
| Completed | 2006 |
| Acreage | 9.74 |
| Building Size (sq ft) | 147,000 |
| Nearest Airport | 7 Miles from Dulles International Airport |
| Critical Power | |
| Total MW | 13 |
| Building Description | |
| Parking | 213 |
| # of Stories | 1 |
| Loading Area and Docks | 2 Loading Bays |
| Elevators | No |
| Ceiling Height | 10 ft |
| Data Center Area Description | |
| Raised Floor Area | 79,600 |
| # of Quadrants | 4 |
| Raised Floor Height | 42" |
| UPS Systems | |
| Description | 12 Rotary power systems with 1,300 kW of critical output, 500 kW of essential output |
| Redundancy | N+2 redundancy |
| Generators | |
| Description | 5 diesel-powered emergency generators with 2,000 kW capacity |
| Redundancy | N+2 |
| Utility Power | |
| Dominion Virginia Power - 34.5 kV | |
| Heat Rejection systems (AC) | |
| Description | Water cooled chilled water cooling system, capacity 7,200 Tons |
| Redundancy | N+2 |
| On site Fuel | |
| # of Gallons | 100,000 gallons |
| # of Hours | Nominal 55 Hours |
| Fire Protection | |
| Extensive pre-action zoned dry-pipe fire protection system with subfloor, room, and above ceiling smoke detectors | |
| Security | |
| Building and Perimeter | Bullet resistant protection at security check-in, front window areas and loading dock |
| Space Security | Staffed 24/7 with separate security lobby |
| Access Control | Electronic Security features with card key access |
| Alarm System | Yes |
| CCTV | Camera Surveillance |
| PDUs | |
| 300-kVA Power Distribution Units with Integral Static Transfer Switches | |
| Tenant Office Space | |
| Available | |
| Communications | |
| * 2 redundant and diverse POE for Carriers with no single point of cable plant failure | |
| Expansion Potential | |
| No | |