ACC4
Ashburn, VA
ACC4 is situated on 17 acres of land at the Ashburn Corporate Center in Loudoun County, Virginia. Ground-up development began in 2006. We consider ACC4 to be our prototype for future ground-up development projects. We believe that its flexible design and enhanced power and cooling capacity make it one of the leading data center facilities in the world. The raised square footage is divided into 20 separate computer rooms, each of which is served by an independent and dedicated critical electrical backup system. This design enables each computer room to function independently and provides us with greater pricing power and the ability to structure flexible leases to meet the demands of our tenants.
In the aggregate, ACC4 will consist of approximately 300,000 gross square feet (not including 40,000 square feet dedicated to housing generators) and 171,300 raised square feet, with a critical load of 36.4 MW. The first phase of this facility, or ACC4 Phase I, was completed on July 1, 2007. ACC4 Phase I comprises approximately 150,000 gross square feet and 85,700 raised square feet with an aggregate critical load of 18.2 MW divided among 10 computer rooms as follows: 2.275 MW going to each of six computer rooms and 1.1375 MW to each of the remaining computer rooms. ACC4 Phase II with an aggregate critical load of 18.2 MW was completed November 1, 2007. Phase I and Phase II are complete and the building is operational.
Specifications
| Property | |
|---|---|
| Location | Ashburn, VA |
| Completed | 2007 |
| Acreage | 17.15 |
| Building Size (sq ft) | 348,464 |
| Nearest Airport | 7 Miles from Dulles International Airport |
| Critical Power | |
| Total MW | 36.4 |
| Building Description | |
| Parking | 153 |
| # of Stories | 1 plus penthouse |
| Loading Area and Docks | 3 Loading Bays |
| Elevators | 1 freight Elevator |
| Ceiling Height | 15-22 ft |
| Data Center Area Description | |
| Raised Floor Area | 171,200 |
| # of Quadrants | 8 |
| Raised Floor Height | 48" |
| UPS Systems | |
| Description | 32 Rotary power systems with 1300 kW of critical output |
| Redundancy | N+2 |
| Generators | |
| Description | 32 diesel-powered emergency generators with 2,250 kW capacity |
| Redundancy | N+2 |
| Utility Power | |
| Dominion Virginia Power - 34.5 kV | |
| Heat Rejection systems (AC) | |
| Description | Water cooled chilled water cooling system with multiple air handler units, capacity 17,280 Tons |
| Redundancy | N+2 |
| On site Fuel | |
| # of Gallons | 4 x 50,000 gallon underground diesel storage tanks |
| # of Hours | Nominal 55 Hours |
| Fire Protection | |
| Laser based Very Early Smoke Detection (VESDA) and a dual action sprinkler system | |
| Security | |
| Building and Perimeter | Bullet resistant protection at security check-in, front window areas and loading dock |
| Space Security | Staffed 24/7 with separate security lobby |
| Access Control | Electronic Security features with card key access |
| Alarm System | Yes |
| CCTV | Camera Surveillance |
| PDUs | |
| Dual Input 300kVA PDU's - 600 Volt Primary | |
| Tenant Office Space | |
| Available | |
| Communications | |
| * 4 redundant and diverse POE for Carriers with no single point of cable plant failure | |
| * 42 carriers available | |
| Expansion Potential | |
| Yes | |